CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-11
disconnect switch to the surface of the unit. If the
factory installed, non-fused service switch option was
purchased, the main power and ground connection
shall be located at the non-fused service switch,
otherwise, the main power connection shall be
located as stated below.
Each unit is provided with pilot hole(s) in the main
power and control panel for connection of the eld-
wiring. These pilot holes are located near the electri-
cal box and a label stating “MAIN POWER INPUT”
is in close proximity. Terminate the main power wires
at the line side of the main power distribution block
located within the electric box. A separate equipment
ground lug is provided within the electrical box for
termination of the earth ground wire.
2.7.1.1 Single-Phase Units 208/230V
Units that are designed for a 208V-supply voltage
must have a tolerance that is within -5% and +10%.
If the measured supply voltage is 230V, the unit
can operate with a tolerance of ±5% if the following
change is performed. The control transformers within
the system must have the primary wire connected to
its respective 240V tap instead of the 208V tap.
2.7.1.2 Single-Phase Units 277V
Single-phase units require that the hot leg of power
be connected to terminal L1 and the neutral wire to
terminal L2 of the main power distribution block.
2.7.1.3 Single-Phase Units (208/230V) with
277/230V Buck/Boost Transformer
Applications (See Figure 6)
Certain applications may require the purchase of a
unit designed for a 208V, 1PH, 60Hz power supply
and supplied with a 277V/230V buck/boost trans-
former. This con guration allows the equipment to
operate from a customer supplied 277V, 1PH, 60Hz
power supply. The purpose of the buck/boost trans-
former is to convert the incoming 277V, 1PH, 60Hz
power supply to the required 230V, 1PH, 60Hz power
supply for unit operation. If the incoming power sup-
ply is within the range of 277V plus 5%, the control
transformers within the system must have the primary
wire connected to its respective 240V tap instead of
the 208V tap.
NOTE
Prior to operation, an adequate unit-to-earth
earth ground must be connected to the unit
Figure 6- Transformer Schematic