(Mar, 2012)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
ir Technology Systems, Inc.
2-3
Mount the thermostat upright on an inside wall within
the conditioned room that best represents the aver-
age room temperature. In most cases, the thermostat
should be located near the common return air grille.
Mount the thermostat at least 18 inches from an
outside wall and approximately 5 ft. above the fl oor.
Follow the steps below to mount. Instructions for wir-
ing the unit and setting the dip switches are provided
in Section 2.7, Utility Connections.
1. Unlatch the thermostat from the base. Remove
the cover plate and, using a fl at head screw-
driver, gently insert into the latch access slot
(bottom of base) until the lock tab disengages.
2. Pry up the handle of the screwdriver to separate
the thermostat panel from the base. Grip the bot-
tom corners of the thermostat panel to remove
from base.
3. Place the base temporarily over the wire hole
opening in the wall. Level the base and mark
location through the two provided mounting slots.
CAUTION
Do not touch the temperature sensor on the
bottom left corner of the thermostat. The sensor
can be damaged if handled improperly.
4. If using the supplied anchors, drill two 3/16 inch
holes, tap in wall anchors. If only the supplied
screws are being used, drill two 3/32 inch holes.
5. Fasten the base to the wall using the supplied
screws.
6. Reinstall thermostat to base.
2.4.3.2 Humidistat/Dehumidistat (Optional
Supplied with A-Tech-1.1/1.2 Thermostat)
Mounting of the humidistat and dehumidistat is
performed in the same manner. Mount the humidi-
stat and/or dehumidistat (as described in Section
2.4.3.1) to a wall within the conditioned room that
best represents the average humidity of the space. In
most cases, the humidistat and dehumidistat should
be located near the common return air grille. Mount
the humidistat and dehumidistat at least 18” from an
outside wall and approximately 5 ft. above the fl oor.
Controls may be installed either on a fl ush switch box
or on a surface switch box. Follow the steps below to
mount. Instructions for wiring of unit are provided in
Section 2.7, Utility Connections.
1. Pull dial knob off, loosen screw (located at bot-
tom of unit) and remove cover.
2. Make wiring connections (see Section 2.7).
3. Mount with the two #6 screws provided.
4. For external setpoint, reinstall cover, tighten
screw, and replace dial knob.
5. For internal setpoint:
a. Turn dial plate to desired setting and tighten
dial lock screw.
b. Break off dial shaft at undercut.
c. Remove insert from cover.
d. Remove protective backing from adhesive on
the blank insert provided and press fi rmly in
place on cover.
e. Reinstall cover assembly and tighten screw. (If
additional security is required an Allen screw
and wrench are provided.)
f. Remove protective cover from face of cover
insert.
2.4.3.3 Advanced Controller
(E² Microprocessor)
If your unit is equipped with an E² controller, a
separate manual is sent in the unit data package
provided with your unit. The controller display may be
fi eld mounted to a wall within the conditioned space
or it may be located outside the conditioned space
if desired. Refer to the supplemental instructions
provided with the mounting kit when mounting the
controller display. When locating the display panel,
consider the length of wire to be used. As an option,
a 30 foot, 75 foot or 150 foot long cable may be
provided by SATS.
2.4.4 Optional Equipment
NOTE
Do not mount any optional equipment on the
A/C unit’s access panels.
2.4.4.1 Transformer
The buck/boost transformer provided is encapsulated
and can be installed indoors or outdoors. If installed
outdoors, the unit should be installed with the wiring
compartment down to prevent entrance of moisture.
For indoor fl oor installation the unit may be installed
horizontally for ease of making wire connections.
Each transformer has keyhole mounting slots for
mounting with bolts to desired surface (wall, fl oor or
other structure capable of supporting its weight).