CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-11
to the surface of the unit. If the factory installed, non-
fused service switch option was purchased, the main
power and ground connection shall be located at the
non-fused service switch, otherwise, the main power
connection shall be located as stated below.
Each unit is provided with pilot hole(s) in the main
power and control panel for connection of the field-
wiring. These pilot holes are located near the electrical
box and a label stating "MAIN POWER INPUT" is in
close proximity. Terminate the main power wires at the
line side of the main power distribution block located
within the electric box. A separate equipment ground
lug is provided within the electrical box for termination
of the earth ground wire.
2.7.1.1 Single-Phase Units 208/230V
Units that are designed for a 208V-supply voltage must
have a tolerance that is within -5% and +10%. If the
measured supply voltage is 230V, the unit can operate
with a tolerance of ±5% if the following change is
performed. The control transformers within the system
must have the primary wire connected to its respective
240V tap instead of the 208V tap.
2.7.1.2 Single-Phase Units 277V
Single-phase units require that the hot leg of power be
connected to terminal L1 and the neutral wire to
terminal L2 of the main power distribution block.
2.7.1.3 Single-Phase Units (208/230V) with
277/230V Buck/Boost Transformer
Applications (See Figure 6)
Certain applications may require the purchase of a unit
designed for a 208V, 1PH, 60Hz power supply and
supplied with a 277V/230V buck/boost transformer.
This configuration allows the equipment to operate
from a customer supplied 277V, 1PH, 60Hz power
supply. The purpose of the buck/boost transformer is
to convert the incoming 277V, 1PH, 60Hz power
supply to the required 230V, 1PH, 60Hz power supply
for unit operation. If the incoming power supply is
within the range of 277V plus 5%, the control trans-
formers within the system must have the primary wire
connected to its respective 240V tap instead of the
208V tap.
NOTE
Prior to operation, an adequate unit-to-earth earth
ground must be connected to the unit
Figure 6- Transformer Schematic