CeilAir CW series Betreibershandbuch Seite 14

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 60
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 13
(©July, 2008)
CeilAiR OHS Series Installation, Operation & Maintenance Manual
A
ir Technology Systems, Inc.
2-3
NOTE
SATS supplied thermostats/controls do not con-
tain mercury.
Mount the thermostat upright on an inside wall within
the conditioned room that best represents the average
room temperature. In most cases, the thermostat
should be located near the common return air grille.
Mount the thermostat at least 18 inches from an
outside wall and approximately 5 ft. above the floor.
Follow the steps below to mount. Instructions for
wiring the unit and setting the dip switches are
provided in Section 2.7, Utility Connections.
1. Unlatch the thermostat from the base. Remove
the cover plate and, using a flat head screwdriver,
gently insert into the latch access slot (bottom of
base) until the lock tab disengages.
2. Pry up the handle of the screwdriver to separate
the thermostat panel from the base. Grip the
bottom corners of the thermostat panel to remove
from base.
3. Place the base temporarily over the wire hole
opening in the wall. Level the base and mark
location through the two provided mounting slots.
CAUTION
Do not touch the temperature sensor on the bot-
tom left corner of the thermostat. The sensor
can be damaged if handled improperly.
4. If using the supplied anchors, drill two 3/16 inch
holes, tap in wall anchors. If only the supplied
screws are being used, drill two 3/32 inch holes.
5. Fasten the base to the wall using the supplied
screws.
6. Reinstall thermostat to base.
2.4.3.2 Humidistat/Dehumidistat (Optional Sup-
plied with A-Tech-1.1/1.2 Thermostat)
Mounting of the humidistat and dehumidistat is
performed in the same manner. Mount the humidistat
and/or dehumidistat (as described in Section 2.4.3.1)
to a wall within the conditioned room that best repre-
sents the average humidity of the space. In most
cases, the humidistat and dehumidistat should be
located near the common return air grille. Mount the
humidistat and dehumidistat at least 18” from an
outside wall and approximately 5 ft. above the floor.
Controls may be installed either on a flush switch box
or on a surface switch box. Follow the steps below to
mount. Instructions for wiring of unit are are provided in
Section 2.7, Utility Connections.
1. Pull dial knob off, loosen screw (located at bottom
of unit) and remove cover.
2. Make wiring connections (see Section 2.7).
3. Mount with the two #6 screws provided.
4. For external setpoint, reinstall cover, tighten
screw, and replace dial knob.
5. For internal setpoint:
a. Turn dial plate to desired setting and tighten
dial lock screw.
b. Break off dial shaft at undercut.
c. Remove insert from cover.
d. Remove protective backing from adhesive on
the blank insert provided and press firmly in
place on cover.
e. Reinstall cover assembly and tighten screw. (If
additional security is required an Allen screw
and wrench are provided.)
f. Remove protective cover from face of cover
insert.
2.4.3.3 Advanced Controllers
(C-Tech 10, A-Tech-20 or C6000)
If you purchased this option, a separate manual is
sent in the unit data package affixed to your unit. Refer
to that manual and the electrical drawing(s) provided
when mounting the controller display. The controller
display may be field mounted to a wall within the
conditioned space or it may be located outside the
conditioned space if desired. When locating the
sensor, consider the length of wire to be used. As an
option, a 30 foot, 75 foot or 150 foot long cable may be
provided by SATS.
2.4.4 Optional Equipment
NOTE
Do not mount any optional equipment on the
A/C unit’s access panels.
2.4.4.1 Transformer
The buck/boost transformer provided is encapsulated
and can be installed indoors or outdoors. If installed
outdoors, the unit should be installed with the wiring
compartment down to prevent entrance of moisture.
For indoor floor installation the unit may be installed