Guide Spec's - Standard Equipment
Guide Specifications - Standard Equipment
3-3
The compressor shall be complete
with charging and service schraeder
ports, internal vibration isolation,
internal thermal overloads, internal
pressure relief valve, internal dis-
charge gas vibration eliminator and
external vibration mounting isolation.
Chilled Water Systems
(Models OHS-()-C)
Cooling Coil:
The chilled water coil shall be con-
structed of seamless drawn copper
tubes, mechanically bonded to tem-
pered aluminum fins for maximum
heat transfer. Coil end plates shall be
hot dipped galvanized.
The cooling coil shall be mounted in
an insulated stainless steel conden-
sate drain pan.
Control Valve:
Cooling capacity shall be controlled
by a factory installed slowly opening
and slowly closing 2-way motorized
control valve rated for a maximum
300 psig w.w.p.
(Note: Please refer to page 3-10 for ad-
ditional chilled water valve options.)
Blowers / Motors
Direct Drive Systems
The blower(s) shall be direct driven
with double width, double inlet hous-
ing and forward curved blades. The
blower(s) shall be dynamically and
statically balanced to minimize vibra-
tion and operate in the Class I range.
The blower(s) shall be corrosion
protected with a painted housing and
impeller wheel.
The three speed (208V) evaporator
motor shall be factory wired for the
correct speed to produce the speci
-
fied air quantity. The motor(s) shall
have internal overload protection.
(277V & 460V direct-drive motors shall be
2-speed.)
Belt Driven Systems
The blower(s) shall be belt driven with
double width, double inlet hous-
ing and forward curved blades and
permanently lubricated ball bearings
sized for an average 100,000 hours
of service life. The blowers shall be
dynamically and statically balanced to
minimize vibration and operate in the
Class I range.
The blower(s) shall have an adjust-
able base for belt tensioning and a
locking system to prevent the mo-
tors from moving. The motors’ drive
sheaves shall have an adjustable pitch
to change the speed of the blowers.
The motor(s) shall be 1725 RPM and
shall have overload protection and
a minimum NEMA service factor of
1.15.
Temp & Humid Control
The standard CeilAiR system is con-
figured as a "cooling only" system.
Heating, reheating and/or humidity
control can be optionally added to
provide total space temperature and
humidity control. (Please see pages
3-5 thru 3-7 for more details.)
A-Tech-1.1
Standard
single stage
DX and non-
proportional
CW Heat/Cool
programmable
digital thermo-
stat.
A-Tech-1.2
Standard dual
stage DX Heat/
Cool program-
mable digital
thermostat.
C-Tech-10
Optional
single or dual
stage DX or
non-propor-
tional CW
Temperature and Humidity Micro-
processor Controller with alarms.
A-Tech-20 & C6000
Optional all pur-
pose Advanced
Temperature
and Humidity
Microprocessor
Controllers with
alarms and op-
tional remote
BMS com-
munications
connections.
(NOTE: Please refer to pages 3-6
& 3-7 for additional specification
details on all CeilAiR ceiling AC
control options.)